Aquality Solutions  

Data Legend

A

Water System Name
B Last Collection Date (LC)
  Shows the most recent collection date from one or more samples used in these results. Frequency of these collections vary. A detailed list of collection dates can be found at the bottom of the page.
C Contaminant
D Maximum Contaminant Level (MCL)
  This is the highest level allowed in drinking water, as designated by the EPA.
E Unit of Measure (µg/L and mg/L)
  Contaminants are measured in micrograms per liter (µg/L) or milligrams per liter (mg/L). If a particular contaminant is measured in µg/L, all records in that column will also be measured in µg/L.
F Concentration Level
  Compare this number to the MCL to see how your water measures up to EPA standards.
  Data Legend:

ZERO: Concentration level is less than the Method Detection Limit or Minimum Reporting Level and is considered a non-detect.

dash N/A: No record is available.
mid MID: Concentration level is over half of the MCL.
high HIGH: Concentration level is over 3/4 of the MCL.
over OVER: Concentration level exceeds the MCL.


 

Vermilion County (back to county map)

Allerton
Alvin
Aqua Illinois—Indianola
Aqua Illinois—Vermilion County
Bismarck Community Water District
Catlin
East Lynn Community Water System
Fairmount
Fithian
Georgetown

Hoopeston
Oakwood
Olivet PWD
Potomac
Rankin
Ridge Farm
Rossville
Sidell
Vermilion Grove Waterworks
Westville


.MCL
10
2000
1300
4000
1000
15
150
2
100
10
9000
500
.Key
As
Ba
Cu
F
Fe
Pb
Mn
Hg
Ni
N
Na
S
 
Arsenic
Barium
Fluoride
Iron
Lead
Manganese
Mercury
Nickel
Nitrate-Nitrite
Sodium
Sulfate

.Allerton
.LC: 01/26/10*

8.29
high

75.9

0

194

1240
over
0

50.6

0

0

0

9.11

81.2

.Alvin
.LC: 01/26/10*

31
over
224

0

560

2150
over
0

69.7

0

0

0

39.7

11.9

.Aqua Illinois—
.Indianola
.LC: 07/15/09*

0

230

230

990

330

2

100
high
0

12

0

26

77

.Aqua Illinois—
.Vermilion County
.LC: 01/15/10*

0

4

22

880

0

0

0

0

0

7.5
high
6.7

32

.Key
As
Ba
Cu
F
Fe
Pb
Mn
Hg
Ni
N
Na
S
.MCL
10
2000
1300
4000
1000
15
150
2
100
10
9000
500

.Bismarck
.Community
.Water District
.LC: 04/19/10*

6.52
mid
175

135.7

992

0

0

17.6

0

0

0

109

20.4

.Catlin
.LC: 07/11/07

-

-

0

-

-

0

-

-

-

-

-

-

.East Lynn
.Community
.Water System
.LC: 09/30/09*

2.46

20.3

0

192

135

0

38.3

0

0

0

54

258
mid

.Fairmount
.LC: 04/19/10*

0

68.9

0

241

72.9

0

0

0

0

0

43.4

88.6

.Key
As
Ba
Cu
F
Fe
Pb
Mn
Hg
Ni
N
Na
S
.MCL
10
2000
1300
4000
1000
15
150
2
100
10
9000
500

.Fithian
.LC: 09/16/09*

1.88

82.5

0

1290

0

0

0

0

0

0

14.1

0

.Georgetown
.LC: 10/13/09*

0

57

94

1200

0

1.7

0

0

0

3.1

22

42

.Hoopeston
.LC: 08/03/09*

6.2
mid
86

220

1100

510
mid

0

29

0

5.6

0.11

24

30

.Oakwood
.LC: 06/03/09*

0

37

1000
high
310

15

14
high
0

0

0

7.9
high
10

56

.Key
As
Ba
Cu
F
Fe
Pb
Mn
Hg
Ni
N
Na
S
.MCL
10
2000
1300
4000
1000
15
150
2
100
10
9000
500

.Olivet PWD
.LC: 09/25/07

-

-

126.8

-

-

11.21
mid
-

-

-

-

-

-

.Potomac
.LC: 08/24/09*

1.31

15.5

0

1040

113

0

0

0

0

0.942

82.2

572
over

.Rankin
.LC: 05/20/09*

0

144

126.1

1220

998
high
0

46.8

0

0

0

43.1

10.3

.Ridge Farm
.LC: 08/18/09*

0

120

415.7

830

0

0

12

0

0

0

5.6

3

.Key
As
Ba
Cu
F
Fe
Pb
Mn
Hg
Ni
N
Na
S
.MCL
10
2000
1300
4000
1000
15
150
2
100
10
9000
500

.Rossville
.LC: 04/06/10*

3

120

630

370

14

0

38

0

5

0

19

12

.Sidell
.LC: 02/23/10*

0

18.9

0

224

0

0

0

0

0

6.11
mid

5.37

64.3

.Vermilion Grove
.Waterworks
.LC: 09/17/08

-

-

0

-

-

0

-

-

-

-

-

-

.Westville
.LC: 06/17/08*

0

18

22

933

0

0

0

0

0

-

0

54.2

.Key
As
Ba
Cu
F
Fe
Pb
Mn
Hg
Ni
N
Na
S
.MCL
10
2000
1300
4000
1000
15
150
2
100
10
9000
500
Other Reports: ChampaignFordIroquoisKankakeeLivingstonMcLeanPiattVermilion

*Collection dates and sample locations can be found in this PDF: Water Data PDF Vermilion County

°For simplicity, only one sample of lead and copper is given per water system. Multiple samples are usually taken from several different locations within each water system. Since the concentration levels vary according to location, we encourage you to visit the Illinois EPA website to determine lead and copper levels nearest your home.

More information about drinking water contaminants can be found on the U.S. Environmental Protection Agency website.

All records were compiled from the Illinois EPA Drinking Water Watch, and are accurate as of May 2010.